If you already have a Gas line installation but you don't know if its legal? Compare it to the following diagrams or give us a call to make sure.

 

Outside placement

Containers shall be at least

a) 1 m away from  any  opening  (into  a  building)  that  is  below  the  level  of  the  container  valve,  e. doors, windows and airbricks, b) 2 m away from any drain, pit or manhole,

c) 3 m away  from  the  property  boundary,  unless  the  boundary  has  a  firewall,  in  which  case  the  containers  could  be  next  to  the  firewall  (see  figure 8),  and  where  there  are  only  two  containers,  the boundary distance can be reduced to 1 m, and

d) 3 m away from any opening (or window) directly above the containers. The 3 m distance from the top of the cylinder, valve connection or the manifold whichever is the higher, to the bottom of the window(s) may be reduced to a minimum of 300 mm providing that

i) a non-combustible  roof  (see  SANS  10400)  is  installed  between  the  containers  and  the    The  roof  shall  extend  beyond  the  cylinder(s)  such  that  when  measured  from  the  valve connection and around the roof to the nearest point of the window a minimum of 1,5 m safety distance shall be obtained, or


ii) the window  frames  shall  be  steel  and  the  total  size  of  the  glazing  does  not  exceed  1  Glazing  shall  be  of  wire  woven  glass  not  larger  than  450  mm  ×  450  mm  per  pane.  Such windows shall not be openable.

e) where a roof  is  installed  over  the  cylinders  there  shall  be  sufficient  space  above  the  cylinder  valves  to  facilitate  the  exchange  of  Roof structures of concrete shall not be installed above the manifold or cylinder

f) 5m away from a switchable electrical point i.e. plug socket, Inline power isolator, Aircon units, Pool pumps, Water pumps etc. Note, a wall light only needs to be 1.5m to the left/right of the bottles, or 1.5m above the bottles.

Inside placement

Additional Info

1) If an instillation consist of copper, Only Class 1 or 2 gas copper piping Is to be used. The copper tubing is required to have markings showing the specs.

2) Copper lines are required to be sleeved/protected if it’s to enter through a wall, Concrete or underground. This stops the copper from corroding.

3) All Pex-Al-pex manufactured to standards accepted for use on Lp Gas installations must be sleeved if it is in any contact with Sunlight/UV.

4) In the event that a gas line is required to run in a roof where heat is impractical, it is required to use corrugated stainless steel gas pipe that is protected with no joins from entry to exit.

5) In a domestic installation, it is required to have a shut off valve/Isolation valve for every appliance connected to the gas line.

6) Flexible hose may not be more than 2m and may not go through any partition at all. This includes Wood, Dry walling, Concrete etc.

7) Where LPG containers are permanently installed or stored in a building, the type of building (In accordance with SANS 10400-A, see also annex B) and the corresponding size of the container(s) shall be as follows:

  1. a) Flats (H3): a maximum of 9 kg per flat;
  2. b) Houses (including cluster housing and group housing (not exceeding two storeys, a total of 19Kg's per unit.

8) A total of 100kg's is allowed outside per a ERF number. If a property has more than 100 kg's, The property will require approval from the fire department.

Water heater placement

Cylinder placement specs for under a window

Cylinder placement specs for under electric fencing

Cylinder distances required from a boundary

Cage Requirements

Domestic installations do not require that the cylinders be placed in a cage but shall be secured in such a manner so as not to accidentally fall over. However where public access to the cylinders is possible, the cylinders and manifold, if fitted, shall be in a locked cage or fenced area that meets the requirements.

6) Flexible hose may not be more than 2m and may not go through any partition at all. This includes Wood, Dry walling, Concrete etc.

7) Where LPG containers are permanently installed or stored in a building, the type of building (In accordance with SANS 10400-A, see also annex B) and the corresponding size of the container(s) shall be as follows:

  1. a) Flats (H3): a maximum of 9 kg per flat;
  2. b) Houses (including cluster housing and group housing (not exceeding two storeys, a total of 19Kg's per unit.

8) A total of 100kg's is allowed outside per a ERF number. If a property has more than 100 kg's, The property will require approval from the fire department.